Message Contents Solution<br />
Solve the problem by examining<br />
Error code received<br />
An error code was sent to the link the CPU error code.Or, refer to<br />
module by the CPU of the PLC. instruction manual of link module<br />
manufactured. *1<br />
Break<br />
The PLC's SD (TXD) is stuck in low Examine the connection between<br />
level.<br />
the PLC's SD (TXD) and the<br />
<strong>ZM</strong> series RD (RXD).<br />
You specified an address that exceeds Check the type and range of<br />
Invalid memory<br />
the memory range of the PLC that you memory that you set.<br />
(applicable to Mitsubishi CPU)<br />
are linked to.<br />
The PLC currently being supported Confirm whether or not the<br />
Invalid CPU model<br />
does not have a corresponding CPU. CPU that you are using can be<br />
(applicable to Mitsubishi CPU)<br />
used with the <strong>ZM</strong> Series.<br />
Format<br />
Compare<br />
(applicable to HIDIC S10)<br />
NAK<br />
(applicable to A B type PLC)<br />
TNS discrepant<br />
(applicable to A B type PLC)<br />
Communication error<br />
Count error<br />
(applicable to Mitsubishi CPU<br />
/Q link unit)<br />
Command error<br />
(applicable to Mitsubishi CPU<br />
/Q link unit)<br />
Invalid cassette<br />
(applicable to Mitsubishi ACPU)<br />
Password error<br />
(applicable to Mitsubishi QCPU)<br />
Check I/F driver<br />
(applicable to I/F driver for<br />
Simulator)<br />
The code of the received data is invalid.<br />
Transmission data and received data<br />
are different.<br />
An NAK code is received.<br />
Transmitted TNS data and received<br />
TNS data are not in agreement.<br />
An unclear communication error is<br />
detected.<br />
The expected data amount is different<br />
from the count value.<br />
The response code differs from the<br />
expected code.<br />
This cassette is not included in the<br />
memory cassettes currently being<br />
supported.<br />
The password is incorrect.<br />
When sending a commucation request<br />
to a personal computer (simulator),<br />
there is no reply from a personal<br />
computer.<br />
Check 1, 2, 3 described below.<br />
Check 1, 2, 3 described below.<br />
Check 1, 2, 3 described below.<br />
Check 1, 2, 3 described below.<br />
Check 1, 2, 3 described below.<br />
Check 1, 2, 3 described below.<br />
Check 1, 2, 3 described below.<br />
Contact the technical support<br />
department.<br />
Contact the technical support<br />
department.<br />
If a simulator is not used, transfer<br />
the I/F driver for PLC again.<br />
[Solutions]<br />
1) Confirm link unit settings.<br />
(After making settings, cut power to the PLC.)<br />
2) Go to editor (<strong>ZM</strong>-<strong>71SE</strong>) and confirm [Comm. Parameter] settings under [System Setting].<br />
3) If errors only occur from time to time, it is possible that there is a noise based communication error.<br />
* If you still cannot solve the error even after following the suggestions above, contact your nearest<br />
distributor of Sharp Corporation.<br />
*1: If the error message “Error code received” appears, one possible cause is a format error in the command<br />
that was sent.<br />
Ex.: Sharp PC — Receive code “01”<br />
Mitsubishi PC — Receive code “06”<br />
Reason; If a higher device number is specified on the screen for a PC model with a lower device number,<br />
there will not be a device number available for the model with the lower device number, and the link<br />
module will return an error signal.<br />
Change the device number that is assigned to one that is outside the PC range on the screen.<br />
For details about other error codes, see the error code list for each link module.