Message Contents Solution<br />

Solve the problem by examining<br />

Error code received<br />

An error code was sent to the link the CPU error code.Or, refer to<br />

module by the CPU of the PLC. instruction manual of link module<br />

manufactured. *1<br />

Break<br />

The PLC's SD (TXD) is stuck in low Examine the connection between<br />

level.<br />

the PLC's SD (TXD) and the<br />

<strong>ZM</strong> series RD (RXD).<br />

You specified an address that exceeds Check the type and range of<br />

Invalid memory<br />

the memory range of the PLC that you memory that you set.<br />

(applicable to Mitsubishi CPU)<br />

are linked to.<br />

The PLC currently being supported Confirm whether or not the<br />

Invalid CPU model<br />

does not have a corresponding CPU. CPU that you are using can be<br />

(applicable to Mitsubishi CPU)<br />

used with the <strong>ZM</strong> Series.<br />

Format<br />

Compare<br />

(applicable to HIDIC S10)<br />

NAK<br />

(applicable to A B type PLC)<br />

TNS discrepant<br />

(applicable to A B type PLC)<br />

Communication error<br />

Count error<br />

(applicable to Mitsubishi CPU<br />

/Q link unit)<br />

Command error<br />

(applicable to Mitsubishi CPU<br />

/Q link unit)<br />

Invalid cassette<br />

(applicable to Mitsubishi ACPU)<br />

Password error<br />

(applicable to Mitsubishi QCPU)<br />

Check I/F driver<br />

(applicable to I/F driver for<br />

Simulator)<br />

The code of the received data is invalid.<br />

Transmission data and received data<br />

are different.<br />

An NAK code is received.<br />

Transmitted TNS data and received<br />

TNS data are not in agreement.<br />

An unclear communication error is<br />

detected.<br />

The expected data amount is different<br />

from the count value.<br />

The response code differs from the<br />

expected code.<br />

This cassette is not included in the<br />

memory cassettes currently being<br />

supported.<br />

The password is incorrect.<br />

When sending a commucation request<br />

to a personal computer (simulator),<br />

there is no reply from a personal<br />

computer.<br />

Check 1, 2, 3 described below.<br />

Check 1, 2, 3 described below.<br />

Check 1, 2, 3 described below.<br />

Check 1, 2, 3 described below.<br />

Check 1, 2, 3 described below.<br />

Check 1, 2, 3 described below.<br />

Check 1, 2, 3 described below.<br />

Contact the technical support<br />

department.<br />

Contact the technical support<br />

department.<br />

If a simulator is not used, transfer<br />

the I/F driver for PLC again.<br />

[Solutions]<br />

1) Confirm link unit settings.<br />

(After making settings, cut power to the PLC.)<br />

2) Go to editor (<strong>ZM</strong>-<strong>71SE</strong>) and confirm [Comm. Parameter] settings under [System Setting].<br />

3) If errors only occur from time to time, it is possible that there is a noise based communication error.<br />

* If you still cannot solve the error even after following the suggestions above, contact your nearest<br />

distributor of Sharp Corporation.<br />

*1: If the error message “Error code received” appears, one possible cause is a format error in the command<br />

that was sent.<br />

Ex.: Sharp PC — Receive code “01”<br />

Mitsubishi PC — Receive code “06”<br />

Reason; If a higher device number is specified on the screen for a PC model with a lower device number,<br />

there will not be a device number available for the model with the lower device number, and the link<br />

module will return an error signal.<br />

Change the device number that is assigned to one that is outside the PC range on the screen.<br />

For details about other error codes, see the error code list for each link module.