Chapter 29 : Error Display<br />
[1] Caused on the <strong>ZM</strong> Series (corresponds to page 29-1)<br />
Error messages displayed on the <strong>ZM</strong> Series are as follow :<br />
1Communication error<br />
2Check<br />
3Warning<br />
4System Error(<strong>ZM</strong>80)/device error(<strong>ZM</strong>70)<br />
5Touch switch is active<br />
Communication Error<br />
Communication Error<br />
*When you go to [Comm. Parameter], bring up the [Detail] tab<br />
window and set [Continue] for [Comm. Error Handling], a screen<br />
like the one shown below is displayed. (See page 2-8 in <strong>ZM</strong>-<br />
<strong>71SE</strong> instruction manual.)<br />
Time-Out<br />
Screen No. : Received code No. :<br />
RETRY<br />
Communication Error<br />
Time-Out<br />
This portion of the message changes.<br />
Message Contents Solution Remarks<br />
Time-Out<br />
is not returned within the required<br />
Although a request is sent for<br />
3) Data may be disrupted because of<br />
1) Check the communication parameters.<br />
amout of time.<br />
transmission to the PLC, an answer<br />
noise. Fix noise.<br />
2) Check the cables and wiring.<br />
A<br />
B<br />
Parity An error occurred in parity check. 1) Check the cables and wiring.<br />
A<br />
2) Data may be disrupted because of<br />
noise. Fix noise.<br />
B<br />
3) Data may be disrupted because of<br />
noise. Fix noise.<br />
Framing Although the stop bit must be [1], 1) Check the communication parameters.<br />
it is detected as [0].<br />
2) Check the cables and wiring.<br />
A<br />
B<br />
Overrun After one character is received, 1) Check the communication parameters. A<br />
the next character is received before 2) Data may be disrupted because of<br />
internal processing is completed. noise. Fix noise.<br />
B<br />
Check Code The check code in the PLC response 1) Check the communication parameters. A<br />
was not correct.<br />
2) Data may be disrupted because of<br />
noise. Fix noise.<br />
B<br />
If the above error messages are displayed on the <strong>ZM</strong> series without establishing communication<br />
* between <strong>ZM</strong> and PLC, test the solution of remark "A."<br />
If the error occurs suddenly in communication, test the the solution of remark "B."