Chapter 29 : Error Display<br />

[1] Caused on the <strong>ZM</strong> Series (corresponds to page 29-1)<br />

Error messages displayed on the <strong>ZM</strong> Series are as follow :<br />

1Communication error<br />

2Check<br />

3Warning<br />

4System Error(<strong>ZM</strong>80)/device error(<strong>ZM</strong>70)<br />

5Touch switch is active<br />

Communication Error<br />

Communication Error<br />

*When you go to [Comm. Parameter], bring up the [Detail] tab<br />

window and set [Continue] for [Comm. Error Handling], a screen<br />

like the one shown below is displayed. (See page 2-8 in <strong>ZM</strong>-<br />

<strong>71SE</strong> instruction manual.)<br />

Time-Out<br />

Screen No. : Received code No. :<br />

RETRY<br />

Communication Error<br />

Time-Out<br />

This portion of the message changes.<br />

Message Contents Solution Remarks<br />

Time-Out<br />

is not returned within the required<br />

Although a request is sent for<br />

3) Data may be disrupted because of<br />

1) Check the communication parameters.<br />

amout of time.<br />

transmission to the PLC, an answer<br />

noise. Fix noise.<br />

2) Check the cables and wiring.<br />

A<br />

B<br />

Parity An error occurred in parity check. 1) Check the cables and wiring.<br />

A<br />

2) Data may be disrupted because of<br />

noise. Fix noise.<br />

B<br />

3) Data may be disrupted because of<br />

noise. Fix noise.<br />

Framing Although the stop bit must be [1], 1) Check the communication parameters.<br />

it is detected as [0].<br />

2) Check the cables and wiring.<br />

A<br />

B<br />

Overrun After one character is received, 1) Check the communication parameters. A<br />

the next character is received before 2) Data may be disrupted because of<br />

internal processing is completed. noise. Fix noise.<br />

B<br />

Check Code The check code in the PLC response 1) Check the communication parameters. A<br />

was not correct.<br />

2) Data may be disrupted because of<br />

noise. Fix noise.<br />

B<br />

If the above error messages are displayed on the <strong>ZM</strong> series without establishing communication<br />

* between <strong>ZM</strong> and PLC, test the solution of remark "A."<br />

If the error occurs suddenly in communication, test the the solution of remark "B."