Page 327.4.2.6 Sizes. Final plans must show all pipe and duct sizes. Draw ductwork to scale onplans. Provide details of catwalks, ladders, platforms, access panels, and doorsnecessary for operation and maintenance of equipment, valves, and accessories. Showall locations of turning vanes, and all volume, fire and smoke dampers.7.4.2.7 Performance Characteristics. Place performance characteristics for all items ofmechanical equipment in the equipment schedules.7.4.2.8 Schedules. Verify that all schedules reflect the necessary equipment information sothat the contractor can select all of the equipment without referring to a specificmodel/manufacturer’s product. The loads indicated on the schedules are theminimum demand requirements from the design calculations for the building features,instead of the sizing items from the vendor catalog information.7.4.2.9 HVAC. Include complete HVAC control plans. Provide DDC controls drawings asrequired by the design. Include all of the COE standard drawings for each systemtype. When required, provide details of EMCS and final EMCS input/outputsummaries. Sequence of control is permitted on the drawings or in the specifications.In either case, provide sequence of control for all HVAC equipment items. (Note,typical sequence of control is found on the COE standard control drawingstemplates.)7.4.2.10 Air Flow. Where critical, indicate on the drawings the air suction and dischargedirections of such items as fans, air-cooled condensers, and cooling towers.7.4.2.11 Fire Protection Drawings. For normal projects, label fire protection drawings as"PRELIMINARY,” and provide a water flow test and results, sprinkler designdensities, demand areas, specific areas protected, hazard classification of all areas,sprinkler head coverage, zoning requirements, pump sizing and locations, buildingentrances, exact control system locations (must include all locations if shown), anddevice locations.7.4.3 Specifications.Provide a complete set of fully edited specifications from the listing given at the interim design.1 April 2007 Version <strong>Army</strong> <strong>Reserve</strong> DPSR Manual -- <strong>Part</strong> C

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!