FlowCERT (UL)
UL manual - Pulsar Process Measurement
UL manual - Pulsar Process Measurement
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
P823 Totaliser Multiplication Factor<br />
Use this parameter if the totaliser increments by to large or small amount,<br />
enter the factor by which the actual flow rate is multiplied by before<br />
incrementing the totaliser.<br />
E.g. if flowrate is being calculated and displayed in ltrs/second and it is<br />
desired to increment the totaliser in cubic metres select 7 = *1000.<br />
When viewing, the totaliser display will state, “Units are: L*1000”, and the<br />
totaliser will be incremented every 1000 litres<br />
Options are:<br />
Option Description<br />
1= 1/1000 Totaliser will increment every 1/1000 th units of flow<br />
2= 1/100 Totaliser will increment every 1/100 th units of flow<br />
3= 1/10 Totaliser will increment every 1/10 th units of flow<br />
4= 1 (Default) Totaliser will increment every 1 units of flow<br />
5= 10 Totaliser will increment every 10 units of flow<br />
6= 100 Totaliser will increment every 100 units of flow<br />
7= 1,000 Totaliser will increment every 1000 units of flow<br />
8= 10,000 Totaliser will increment every 10,000 units of flow<br />
9= 100,000 Totaliser will increment every 100,000 units of flow<br />
10= 1,000,000 Totaliser will increment every 1,000,000 units of flow<br />
P824 Totaliser Enable<br />
This parameter determines if the totaliser is enabled or not, the options are<br />
as follows:<br />
Option<br />
Description<br />
0 = Off Totaliser will be disabled<br />
1 = On (Default) Totaliser will be enabled<br />
Page 104