Example 1 ‘V’ Notch Weir<br />
In this example it is required to calculate the flow through a Simple<br />
Exponential Device, which on this occasion is a V-Notch Weir. The K factor<br />
for the weir is unknown so ratiometric calculation will be used, there is no<br />
requirement for alarms and the flow rate is to be displayed in Mil USG/day.<br />
The totaliser is to record the flow in 1000’s USG but is not to be displayed<br />
during RUN. The transducer to be used is a dB3.<br />
The distance from the face of the transducer to zero flow (P105) is 40<br />
inches and max head (P704) is 15 inches, maximum flow (P705) is known<br />
to be 2.2 million US gallons/day.<br />
Page 42