The fourth parameter, and fifth parameter, are set to determine the switch<br />
points, “ON” and “OFF” for the relay. See miscellaneous function table<br />
(P211, 221, 231, 241, 251) for further information.<br />
When P211, 221, 231, 241, 251 = 1 (Clock)<br />
P213, P223, P233, P243, P253 - Relay Setpoint 1<br />
Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at which<br />
relay will energise. Default = 00:00 (HH:MM)<br />
P214, P224, P234, P244, P254 - Relay Setpoint 2<br />
Relay Setpoints are entered in Minutes to set Time Period that the relay will<br />
remain ON. Default = 0.00 mins.<br />
When P211, 221, 231, 241, 251 = 2 (Totaliser)<br />
P213, P223, P233, P243, P253 - Relay Setpoint 1<br />
Relay Setpoints are entered as a factor by which the on board totaliser (P820)<br />
should be multiplied by to provide a relay closure. Default = 0.00<br />
P214), P224, P234, P244, P254 - Relay Setpoint 2<br />
Relay Setpoints are entered in seconds to set the time period that the relay will<br />
remain ‘ON’. Default = 0.00 secs.<br />
Page 87