The third parameter for each relay determines the alarm ID for the relay<br />
you wish to set.<br />
P212, P222, P232, P242, P252 - Relay Alarm ID<br />
When P211, 221, 231, 241 251 = 1 (Level), 2 (Rate of Change) or 3<br />
(Temperature.)<br />
This parameter defines which alarm type, or identification, the relay<br />
should respond to, as follows.<br />
Alarm ID Description Setpoints<br />
1=General (Default) Relay goes “ON” when<br />
the value reaches the ON<br />
setpoint and goes “OFF”<br />
when the value reaches<br />
the OFF setpoint.<br />
2= High Relay goes “ON” when<br />
the value rises to the ON<br />
setpoint and goes “OFF”<br />
when the value lowers to<br />
the OFF setpoint.<br />
3= Hi-Hi Same as 2 = High, but<br />
different identifier.<br />
4= Low Relay goes “ON” when<br />
the value lowers to the<br />
ON setpoint and goes<br />
“OFF” when the value<br />
rises to the OFF setpoint.<br />
5= LoLo Same as 4=Lo, but<br />
different identifier.<br />
P213, 223, 233,<br />
243, 253 is ON<br />
Setpoint; P214,<br />
224, 234, 244, 254<br />
is OFF Setpoint<br />
ON> OFF<br />
Relay Setpoints<br />
P213, 223, 233,<br />
243, 253 and P214,<br />
224, 234, 244, 254<br />
Setpoints, can be<br />
set in any order as<br />
the unit ‘knows’<br />
that you are setting<br />
a high level alarm.<br />
ON