P146 Tel. No2<br />
This parameter is used to enter to enter the next 6 digits, following the ‘0’s,<br />
of the telephone number to be dialled. If there are less then 8 digits<br />
following the ‘0’s then just enter the digits required, if there are more than<br />
digits following the ‘0’s then enter the first 6 digits and then proceed to<br />
P147 and enter the remaining digits.<br />
P147 Tel. No3<br />
This parameter is used to enter any remaining digits of the telephone number<br />
to be dialled after completion of P145 and P146 above.<br />
Example<br />
Telephone number to be dialled is: 0 1234 123456<br />
P145 Tel. No. 1 = 1(One ‘0’ at the beginning of the telephone number)<br />
P146 Tel. No. 2 = 123412 (The next 6 digits following the ‘0’s).<br />
P147 Tel. No. 3 = 3456 (Remaining digits of telephone number).<br />
P148 Timed Out<br />
This parameter will set the time period that the unit will wait for a reply<br />
before disconnecting. Default = 90 seconds<br />
P149 Retry No.<br />
This parameter will set the number of times the telephone number will be redialled<br />
if no reply is received. If set to ‘0’ then the number will be re-dialled<br />
continually until a reply is received, if set to ‘-1’ then number will not be redialled<br />
at all. Any other value entered between 1 and 99 will determine the<br />
number of re-dials to be attempted. Default = 0<br />
Page 123