Parameter Default Description<br />
P101<br />
1 = dB3 Type of Transducer to be used.<br />
Transducer<br />
P706<br />
Volume Units<br />
6 = Mil. USG Units of flow as on display and used<br />
P707<br />
Time Units<br />
P104<br />
Measnt Units<br />
P105<br />
Empty Level<br />
P703<br />
Minimum<br />
Head<br />
P704<br />
Max Head<br />
P824<br />
Totaliser<br />
Enable<br />
P816<br />
Totaliser ( R )<br />
for calculations.<br />
1=litres<br />
3=cubic feet<br />
5=US gallons<br />
2 = cubic metres<br />
4 = UK gallons<br />
6 = Mil.USG<br />
4 = per day Units of time that volume units will<br />
be displayed and calculated in.<br />
1= units/sec. 2= units/min.<br />
3= units/hour 4= units/day<br />
5 = inches Units used to enter dimensions, and<br />
displayed where appropriate.<br />
1 = metres 2 = centimetres<br />
3 = millimetres 4 = feet<br />
5 = inches<br />
106.299<br />
inches<br />
Distance from the face of the<br />
transducer to the material at the<br />
bottom of the measuring element.<br />
0.000 inches Distance from empty point (P105) to<br />
zero flow.<br />
101.378<br />
inches<br />
Distance from zero flow to max<br />
flow. It should be noted that any<br />
change to P704 updates P106 Span<br />
and vice versa.<br />
1=On Enables the flow totaliser, P820,<br />
options are 0=Off, 1=On. Note this<br />
totaliser can be viewed during run<br />
via the totaliser “Hot Key” It can be<br />
reset but only via P820, whilst in<br />
“program mode”.<br />
0=No<br />
Enables the totaliser to be displayed<br />
in the auxiliary display whilst in “run<br />
mode”. Note this totaliser is<br />
“resettable”, whilst in “run mode”,<br />
via the totaliser hot key.<br />
Page 34