Temperature<br />
P852 Temperature Source<br />
This parameter determines the source of the temperature measurement. By<br />
default it is set to External Range “A” (P852=4), which will use an external<br />
temperature sensor with range -25˚C to 50˚C. If for any reason, no<br />
temperature input is received, then the Fixed Temp value is used, as set by<br />
P854.<br />
The temperature source can be specifically set as follows:<br />
Option<br />
Description<br />
1 = Automatic Will automatically select transducer<br />
temperature sensor, if available, or fixed<br />
temperature (P854) if no temperature<br />
sensor found.<br />
2 = Xducer Always uses temperature reading from<br />
transducer.<br />
3 = Fixed Always uses fixed temperature (P854)<br />
4 = Ext Range “A”<br />
(Default)<br />
Uses an optional external temperature<br />
sensor with an operating range of -25 o C to<br />
50 o C.<br />
5 = Ext Range “B” Uses an optional external temperature<br />
sensor with an operating range of -25 o C to<br />
125 o C.<br />
P854 Fixed Temperature<br />
This parameter sets the temperature, in degrees centigrade to be used if<br />
P852 (Temperature Source) = 3. Default = 20 o C<br />
Page 109