Bargraph<br />

P829 Bargraph<br />

By default the bargraph will be representative of the reading obtained, as<br />

determined by the Mode P100. This parameter is automatically set to the<br />

correct default option when selecting the Mode P100 and Xducer (P101),<br />

and under normal circumstances will not require changing.<br />

The options, dependant on the value entered for Mode P100, are as follows:<br />

Option<br />

Description<br />

1 = Level Bargraph will be representative of level.<br />

2 = Head (Default) Bargraph will be representative of head.<br />

3 = Flow Bargraph will be representative of flow.<br />

mA Output Parameters<br />

Range<br />

P830 mA Range<br />

This parameter determines the range of the mA output, from the following.<br />

Option<br />

Description<br />

0= Off mA output disabled.<br />

1= 0 to 20 mA mA output directly proportional to the mA mode<br />

(P831), so if the reading is 0% the output is 0 mA. If<br />

the reading is 100% the output is 20 mA.<br />

2= 4 to 20 mA mA output directly proportional to the mA mode<br />

(Default) (P831), so if the reading is 0% the output is 4 mA. If<br />

the reading is 100% the output is 20 mA.<br />

3= 20 to 0 mA mA output inversely proportional to the mA mode<br />

(P831), so if the reading is 0% the output is 20 mA. If<br />

the reading is 100% the output is 0 mA.<br />

4= 20 to 4 mA mA output inversely proportional to the mA mode<br />

(P831), so if the reading is 0% the output is 20 mA. If<br />

the reading is 100% the output is 4 mA.<br />

Page 105