Bargraph<br />
P829 Bargraph<br />
By default the bargraph will be representative of the reading obtained, as<br />
determined by the Mode P100. This parameter is automatically set to the<br />
correct default option when selecting the Mode P100 and Xducer (P101),<br />
and under normal circumstances will not require changing.<br />
The options, dependant on the value entered for Mode P100, are as follows:<br />
Option<br />
Description<br />
1 = Level Bargraph will be representative of level.<br />
2 = Head (Default) Bargraph will be representative of head.<br />
3 = Flow Bargraph will be representative of flow.<br />
mA Output Parameters<br />
Range<br />
P830 mA Range<br />
This parameter determines the range of the mA output, from the following.<br />
Option<br />
Description<br />
0= Off mA output disabled.<br />
1= 0 to 20 mA mA output directly proportional to the mA mode<br />
(P831), so if the reading is 0% the output is 0 mA. If<br />
the reading is 100% the output is 20 mA.<br />
2= 4 to 20 mA mA output directly proportional to the mA mode<br />
(Default) (P831), so if the reading is 0% the output is 4 mA. If<br />
the reading is 100% the output is 20 mA.<br />
3= 20 to 0 mA mA output inversely proportional to the mA mode<br />
(P831), so if the reading is 0% the output is 20 mA. If<br />
the reading is 100% the output is 0 mA.<br />
4= 20 to 4 mA mA output inversely proportional to the mA mode<br />
(P831), so if the reading is 0% the output is 20 mA. If<br />
the reading is 100% the output is 4 mA.<br />
Page 105