To program the <strong>FlowCERT</strong> LITE for Example 2 BS3680 U-Throated<br />
Flume by using the Quick Setup menu, proceed as follows.<br />
If required access the Program Mode<br />
Key in the passcode 1997 and press ENTER<br />
Using the ‘right’ arrow key go to the Quick Setup menu press ENTER and<br />
as prompted, by the questions, select the relevant option and press ENTER.<br />
Question<br />
Option<br />
PMD Type<br />
2 = 3680 Flume<br />
3680 Flumes 3 = U Throat<br />
Calculation<br />
1 = Absolute<br />
No. of Alarms 1 = 1 Alarm<br />
Type Alarm 1 2 = Low<br />
Alarm No 1 1 = Set Relay 1<br />
Xducer<br />
1 = dB3<br />
Volume Units 6 = Mil USG<br />
Time Units<br />
3 = Per Hour<br />
Measnt. Units 5 = inches<br />
Empty Level 35.0 inches<br />
Minimum Head 0.000 inches<br />
Maximum Head 15.0 inches<br />
Total Enable<br />
1 = On<br />
Totaliser ( R ) 1 =Yes<br />
Total Multiplier 7 = 1000<br />
Approach. Dia. 28.0 inches<br />
Throat Dia.<br />
20.0 inches<br />
Throat Len.<br />
40.0 inches<br />
Programming is now complete and the unit can now be returned to the run<br />
mode, press CANCEL until Run Mode? Is displayed on the LCD press<br />
ENTER, and the <strong>FlowCERT</strong> LITE will return to Run Mode.<br />
Note<br />
If relay setpoints do not meet the exact requirements of the<br />
application, they can be modified to suit by pressing ENTER when,<br />
“For More Options Hit Enter”, is displayed, and entering new values<br />
to relay setpoints as required. Alternatively the relevant relay<br />
setpoint can be accessed either by the main menu system or directly<br />
via parameter number and changed as necessary.<br />
Page 48