P210, P220, P230, P240, P250 - Relay Type<br />
This parameter defines what type each relay should be, see the table below<br />
for available options.<br />
Option<br />
Description<br />
0= Not In Use (Default) Relay not in use or programmed and LED<br />
will always be off.<br />
1= Alarm Relay is programmed as an alarm relay,<br />
which will de-energise ON, and energise<br />
OFF. This will ensure an alarm is raised if<br />
the power fails to the unit.<br />
2= Pump Relay is programmed as a pump relay, which<br />
will energise ON, and de-energise OFF.<br />
3= Control Relay is programmed as a control relay,<br />
which will energise ON, and de-energise<br />
OFF.<br />
4= Miscellaneous Relay is programmed as a miscellaneous<br />
relay, which will energise ON, and deenergise<br />
OFF.<br />
Page 74