I. REGULATORY CONTROL FUNCTION BLOCKS

To set the deadband action - Select “Yes” or “No.” The default is “No.” When the

deadband action is set as “Yes,” the hysteresis (HYS) must be set. Hysteresis:

Engineering unit data between 0 and the PV scale span range limit. The default

is the value equivalent to 1.0 % of the PV scale span.

♦ AUT Fallback

The AUT fallback is an error processing function that switches the block

mode from cascade (CAS) or primary direct (PRD) to automatic (AUT)

when the AUT fallback condition is established. Thus the set value of the

control loop can be set by the operator. The AUT fallback condition is

established when the data status of the cascade setpoint value (CSV)

become invalid (BAD) or communication error (NCOM).

♦ Computer Backup Mode

When the computer fail is detected, the function block suspends the action

in the remote cascade (RCAS) mode or remote output (ROUT) mode

temporarily and switches to the computer backup mode.

I.3.6 OUTPUT

♦ Output Change

The output velocity limiter limits the amount of change in the output value

according to the output velocity limit setting. The output velocity limit is a

permissible amount of output change over one scan period. The output

velocity limiter and the bypass for MAN-mode output velocity limiter can

be defined.

• Output Velocity Limiter:

Engineering unit data or percentage within the range from 0 to the

MV scale span setting in positive values only (six significant

figures). The default setting is 100.0 %.

• MAN Mode Output Velocity Limiter Bypass:

Selectable between “Yes” and “No.” Default is “No.”

♦ Auxiliary Output

The auxiliary output is used when output a signal through the SUB

terminal to a destination other than the final control element. The signal is

often used as compensation data to other function blocks, or to the

indicator outside of the FCS, etc. In the Regulatory Control Blocks, the

process variable (PV), change in process variable (∆PV), manipulated

output value (MV), or the change in manipulated output value (∆MV) is

output via the SUB terminal. The connection method is the data setting.

Output Type is selectable from “Positional Output Action” and “Velocity

Output Action.” Default is “Positional Output Action.” When the output

action for auxiliary output is set to “Positional Output Action,” the output

values (MV, ∆MV, PV, or ∆PV) can be set in the connection destination as

YME Training Center I-18

CS3KR3-ENG 1 ST Edition Jan 2002