J. SEQUENCE CONTROL FUNCTION

Figure: Example of Conditional Branch in step sequence

J.2.5 RULE EXTENSION

The number of rules in one sequence table is fixed at 32 and cannot be modified.

However, if the number of rules in a sequence table is not enough to describe

one phase unit, it can be extended in the 32-rule unit by connecting to another

sequence table. The number of rules can be extended for a step-type sequence

table.

♦ Method of Rule Extension

To extend the number of rules, specify a tag name for the rule extension

block (ST16E) in the sequence table setting area of the extending

sequence table (ST16). It does not matter if the number of signals and

signal contents are different between the extending sequence table

(ST16) and extended sequence table (ST16E). The number of rules can

be extended in the 32-rule unit per block. An example of the number of

rules extended to 64 is shown below.

Figure: Examples of Rule Extension

J.2.6 PROCESSING TIMING

A sequence control block and a logic chart block have the following four types of

execution timing:

♦ Periodic Execution (T)

♦ One-Shot Execution (O)

♦ Initial Execution/Restart Execution (I)

♦ Restricted Initial Execution (B)