I. REGULATORY CONTROL FUNCTION BLOCKS

it is. Also, when set to the “Velocity Output Action” type, the value read

back from the connection destination is added to the output value and set

in the connection destination.

♦ MV Display Style

Use the Function Block Detail Builder to set the display form for the

manipulated output value (MV).

• MV Display Style:

Select “Automatic Determination” or “User Define.”

The default is “Automatic Determination.”

When “Automatic Determination” is selected, the engineering unit and

scale range of the manipulated output value (MV) change according to the

connected destination of the OUT terminal. When “User Define” is

selected, set the engineering unit and scale range for the manipulated

output value (MV).

♦ Limit Output in Direction when Clamped

When the data status of the cascade connection destination is CLP+ or

CLP-, the output direction of the manipulated output value (MV) is

restricted, i.e., the value cannot be changed to exceed or falls below the

present output value, so that only the manipulated output value (MV) in

the direction that cancels CLP+ or CLP- is output. Limit output in direction

when clamped is selectable from “Yes” and “No.” Default is “Yes.”

♦ Control Calculation Output Type

A Regulatory Control Block outputs its manipulated output value (MV) or

the vicissitude of that value (∆MV). There are two types output action:

positional and velocity:

• In positional output action, the output value connects to its

destinations unchanged.

• In velocity output action, the amount of change for the

current output (∆MV) is added to the value read back from

the connection destination of the output terminal.

The output operation can be selectable from “positional” or “velocity.”

Default is the “positional” action.

I.3.7 CONNECTION

The wiring configuration done using the control drawing builder appears on this

sheet.

I.3.8 OTHERS – CONSTANT

Constants are preset tuning parameters; they can be set in the Constant text box

on others tab. Up to 1,024 alphanumeric characters can be used for each

YME Training Center I-19

CS3KR3-ENG 1 ST Edition Jan 2002