T. PROJECT COMMON DEFINITION

medium-priority alarm designated for bit position 8, a high-priority alarm cannot

be designated for bit positions 9 to 32.

♦ Color

Choose from 16 colors corresponding to the alarm.

♦ Priority

Designate the alarm priority.

The system-fixed alarm status character string itself cannot be changed, but its

color and priority can be changed. For example, the PID controller block assigns

“HI” to bit position 17. By default this will be processed as a medium-priority

alarm upon its occurrence, and displayed in red. To change the above mediumpriority

alarm to the high-priority alarm and display “HI” in magenta, do the

following:

♦ To change it to the high-priority alarm, use the Alarm Priority Builder. Note

that changes made here will be effective for high-priority alarms of other

function blocks.

♦ In the Alarm Processing Table Builder, select the field for alarm

processing level No.5 for bit position 17, and then select [M: Magenta] for

[Color (5)], and [1: High-priority Alarm] for [Priority (5)]. (The color and the

priority can be changed for any of alarm processing level Nos. 5 to 16.)

Figure: Designation in the Alarm Processing Table Builder

♦ Select the [Alarm] tab in the Function Block Detail Builder, and then select

[5: User defined Alarm Process (5)] at [Alarm Processing Level].