I. REGULATORY CONTROL FUNCTION BLOCKS

♦ Index

This function displays two indexes in the manipulated output value (MV)

scale on the operation monitoring window of the operation and monitoring

function. These are called the manipulated output indexes. By setting

these indexes at the operable limits of the manipulated output values

(MV), they can be used as manipulation guides in the manual mode, or as

guides for verifying normal status in the automatic mode. For a Regulatory

Control Block with manipulated output value (MV), both the high output

limit (OPHI) and low output limit (OPLO) indexes can be set on the tuning

window. These limits are displayed in the operation and monitoring

window of the operation and monitoring function. The indexes may be

defined on the Function Block Detail Builder.

• Set Indexes: Selectable from “Yes” and “No.”

Default is “Yes.”

♦ Scale-Division

The scale divisions may be specified as 1, 2, 3, 4, 5, 7 divisions. Autodivision

may be used.

♦ Upper Equipment Name

The upper equipment name refers to the name of the equipment object

located in the next upper layer of an equipment object in a plant hierarchy.

Specifying an upper equipment name via the Plant Hierarchy Builder

determines the location of an equipment object in the plant hierarchy. Only

custom equipment names can be specified as the upper equipment name.

I.3.3 INPUT

♦ Process variable range; High and low limits

Numerical values of seven digits or less, where the sign or decimal point

takes one digit each. The default is “100.0” for the upper limit and “0.0” for

the lower limit.

♦ Engineering unit

Consists of six or less standard-width characters or three double-width

characters. The default is “%.”

♦ Input Signal Filtering

The digital filter may be defined for each function block in “Input Signal

Filtering” on the Function Block Detail Builder. Input Signal Filtering:

“None,” “Auto,” “1,” “2” and “3.” The default setting is “Auto.”

When Auto is selected; if the IN terminal is connected to I/O module other

than communication module, “Digital Filter Coefficient 1” is used. If the IN

terminal is connected to neither communication module nor I/O module,

no filtering process is performed.

YME Training Center I-11

CS3KR3-ENG 1 ST Edition Jan 2002