G. PROCESS INPUT/OUTPUTS

♦ Service Comment

The service comment is set with IOM Builder. Nothing is set by default. A

string of up to 40 alphanumeric characters or 20 double-byte characters

can be entered. The setting of the service comment may be omitted.

♦ High/Low range and Unit

The lower and upper limit values of the measurement range of the

terminal is set with IOM Builder. The values that can be selected as the

lower and upper limits of the range vary depending on the I/O module

type, signal conversion type, and terminal position. For AAI835 type the

low and high limits are fixed at 4 and 20 mA respectively.

♦ Set details

The details setting of the I/O module are carried out in IOM Builder. The

items that can be selected vary depending on the I/O module type. For

AAI835, the output points can have either direct or reverse setting. If direct

is set, when the output reads 0% the current output to the valve would be

4mA and 100% implies 20mA. If reverse is set, when the output reads 0%

the current output to the valve is 20mA and 100% implies 4mA.

♦ P&ID tag name

Nothing is set by default. A string of up to 16 alphanumeric characters or 8

double-byte characters can be entered. The setting of the P&ID tag name

may be omitted.

♦ Label

The user-defined label can be set for terminals. Nothing is set by default.

This can be used in the control drawings instead of system defined

terminal names, which would difficult to remember. Up to 16 byte

alphanumeric characters can be entered. The setting of the user-defined

label may be omitted and in such case the terminal name should be used

in the control drawing.

The following shows the specification format of the user-defined label:

%%Mnnnn

%%: Unique to the system

M: The third character must be an uppercase character (A through Z).

nnnn: The forth and subsequent characters must be within 13 characters

in a combination of uppercase and lowercase alphanumeric characters (A

through Z, a through z, and 0 though 9).

YME Training Center

G-13

CS3KR3-ENG 1 ST Edition Jan 2002