F. DEFINING FCS CONFIGURATION

♦ Station definition type

Define whether to receive the values of global switches under the control

of other stations if transferred.

• Station definition type:

Choose “0: Not communicate,” or “1: Individual Station

Communication.” The default is 0. When you choose “Individual

Station Communication,” define the communication buffer size to

receive data.

• Individual Station Definition (stations 1 to 64):

Define 32 (bytes) (same value as the buffer size of the present

station defined at the sending station) to receive data, or 0 not to

receive data.

F.3.1 DETAILED SETTING ITEMS

♦ Wind up Time

Windup operation is a preparatory processing for organizing time-series

data that are required for control operations. The function block’s input

processing, control processing, calculation processing and alarm

processing executed during windup operation are executed in the same

manner as in normal operation. All output signal processing, except for the

one that outputs control output signals to the process output terminal, are

executed in the same manner as in normal operation. Sequence table

blocks and logic chart blocks don’t operate while windup operation is

running.

The windup operation time can be set on the FCS Constant Builder.

♦ Wind Up Time: Set 0 to 100 (sec.).

The default is 60 sec.

♦ SEBOL / User C Ratio

The setting of the processing executed in the idle time in FCS’s CPU is

defined in “SEBOL/User C time ratio” on the FCS Constants Builder. This

time ratio is set as “100 %” as default, means the total idle time of FCS’s

CPU is used by SEBOL.

♦ Interval for repeat warning alarms

The repeated warning alarm is a function that retransmits a process alarm

message after a specified time has elapsed during the period between the

alarm occurrence and recovery from the alarm, regardless of whether the

alarm is acknowledged. The purpose of the repeated warning alarm is to

notify the operator that a critical alarming state is continuing. The setting

value is between 0 to 3600 seconds. When 0 is set, repeated warning

alarm function is disabled. Default is 600 seconds

YME Training Center

F-7

CS3KR3-ENG 1 ST Edition Jan 2002