I. REGULATORY CONTROL FUNCTION BLOCKS

♦ PV Overshoot

When the data status of input signal becomes invalid (BAD), the PV

overshoot function overshoots the process variable (PV), or upscale it to

scale high-limit or downscales it to scale low-limit. Select “Overshoot PV”

or “Holding PV.” The default setting is “Holding PV.” With “Holding PV,”

when the data status of process variable (PV) becomes invalid, the last

good process variable is held. Furthermore, when the input signal is not a

process input signal, the operation becomes “Holding PV” even though

“Overshoot PV” is specified.

I.3.4 ALARM

♦ Alarm Level

Designating an alarm processing level to a function block or an element,

the alarms from the function block or the element will have the designated

priority and display the designated color. The definitions for level1 to

level4 are fixed for a whole system. The alarm priorities and colors for

level5 to level16 can be defined by users.

♦ Input Open Alarm

The input open alarm check is a function that determines whether the

input values read from the field by the I/O module is out of the range of the

high and low limit input open detection setpoint values. The high-limit input

open alarm (IOP) is initiated when it is determined that the input value

exceeds the input open high detection setpoint value. Similarly, the lowlimit

input open alarm (IOP-) is initiated when the input value is below the

low-limit input open detection setpoint value. The high and low limit input

open alarm (IOP, IOP-) indicates that a failure such as severed wires in

the detection terminal or transmitter has occurred. IOP alarm detection on

both sides, high, low and no IOP alarm is selected.

♦ PV High-High/Low-Low Limit Alarm

The input high-high and low-low limit alarm check is a function that

determines whether the input process variable (PV) is out of the range of

the high-high and low-low limit alarm setpoint value (HH, LL).

YME Training Center I-12

CS3KR3-ENG 1 ST Edition Jan 2002