I. REGULATORY CONTROL FUNCTION BLOCKS

• No-Conversion Output

The manipulated output value (MV) resulted from the controlcalculation

process is No Conversion output.

• Pulse Width Output Conversion

The changes of manipulated output value (∆MV) is output after

converted into a pulse width signal.

• Communication Output Conversion

The manipulated output value (MV) resulted from the controlcalculation

process is converted into the format compatible with the

destination subsystem.

♦ Tight-Shut Function and Full-Open Function

The Tight-shut function fully close an operation valve and the Full-open

function fully open it when a manipulated output value (MV) is 0% or 100

%. With these functions, an actual tight-shut output value (Ms) is set to a

value less than 0% or greater than 100%, fully closing an operation valve.

And an actual full-open output value (Mf) is set to a value less than 0% or

greater than 100%, fully opening the valve. When set “No” to “Tightshut/full-open

Specifications”, these functions are not added.

Figure: Tight-shut function

Define the Tight-shut/full-open specifications, as below.

• Tight-shut/full-open Specifications:

Choose “Yes” or “No.”

The default setting is “Yes.”

• Output Value for tight-shut (Ms):

The actual output value for tight-shut

Setting range is -17.19 to 117.19 % (5 significant figures). Default is

-17.19 % for direct output setting, and -6.25 % for reverse output

setting.

• Output Value for full-open (Mf):

The actual output value for full-open

YME Training Center I-7

CS3KR3-ENG 1 ST Edition Jan 2002