G. PROCESS INPUT/OUTPUTS

G.2. IOM BUILDER

IOM builder definition for AAI835 IOM is discussed in detail below.

♦ Terminal

A terminal of a process I/O or a Fieldbus I/O can be numbered in

accordance with its physical position and the I/O module location. The

format of a terminal number is as follows.

%Znnusmm

%Z: Identifier of process I/O (Fixed)

nn: Node Number (01 - 10)

u : Unit Number (1 - 8)

s : For a Fieldbus communication module, s stands for segment number (1

-4). When using modules compatible to HART communication, for

measured analog data s=1, while for the data via HART communication

s=2. For other I/O modules s is fixed as 1.

mm: Terminal Number (01 - 64)

♦ Conversion

No conversion is applicable for this type of card.