B. SYSTEM OVERVIEW

B.7. HARDWARE CONFIGURATION

The dip switches for domain and station no. setting for the FCS is found in the

CPU card and has to be set correctly for station address identification as per the

configuration.

Domain no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Station no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0

Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1

Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0

Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0

Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0

Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

Figure : Domain and Station number setting for FCS

The dip switches for domain and station no. setting for the HIS is found in the VL

net control bus card, installed in the PC PCI slot and has to be set correctly for

station address identification as per the configuration.

Domain no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Station no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 Bit 8 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 Bit 7 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0

Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 Bit 6 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0

Bit 6 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 Bit 5 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0

Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Bit 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1

Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0 Bit 1 0 0 1 0 1 1 0 0 1 1 0 1 0 0 1 0

Figure : Domain and Station number setting for HIS.

YME Training Center

B-16

CS3KR3-ENG 1 ST Edition Jan 2002