F. DEFINING FCS CONFIGURATION

identify the HIS for communication among HISs on the control bus. In

normal situation, the automatically determined setting should be used.

172. 16. dd. ss

172: System fixed

16: Identifier showing that the bus type is control bus (fixed)

dd: Domain number

ss: Station number

♦ Control Bus Subnet Mask

The control bus subnet mask is set to “255.255.0.0” as the default setting.

In normal situations, this default setting should be used.

F.2. FCS STATION DEFINITION

The following explains the setting details of FCS station definition.

F.2.1 DEFINITION ITEM

♦ Start condition

The start condition determines which method to be used, initial cold start

or restart, to initiate the FCU, upon turning on the power to FCU, which

was in the power shutoff status. Select one from “MAN (Initial Cold

Start),” “TIME (Restart in case of momentary power failure)” or “AUTO

(Restart).” The default is “MAN (Initial Cold Start).”

MAN (Initial cold

start)

TIME (Restart at

the time of

momentary power

failure)

Start Condition

Prolonged power failure (Momentary

power failure tolerant time-FCS

power failure time)

Momentary power failure

(Momentary power failure tolerant

time>FCS power failure time)

AUTO (Restart) -

-

Start Operation

Initial cold start

Restart

Table: FCS Start condition

Initial Cold start

Initial cold start is to reset all FCS’s internal states and initiates the control

operations from initial status.

YME Training Center

F-5

CS3KR3-ENG 1 ST Edition Jan 2002