F. DEFINING FCS CONFIGURATION

The mode of the block other than MAN is AUT or CAS is selected from

this setting. The default setting is [AUT].

♦ Action Type of SEBOL “drive” Statement

There are 3 action types of SEBOL “drive” statement that can be

specified. In accordance with the block mode of the function block, which

is running SEBOL and the action type specified here, the permission to

output the operation commands to function blocks may be checked.

♦ Setting Options

When using option programs, the programs need to be registered on the

FCS properties setting box. After installing the option programs, the

programs may be listed on the properties setting box for registration.

♦ Blocks with User-Defined Data Items

The user-defined blocks should not be specified in the area that may

duplicate with others in whole FCS. When using the blocks with userdefined

data items (SFC block, unit instrument), a specific area for the

user-defined blocks needs to be specified. [Number of Block Type]

displays the allowed number of block types for the current type of FCS

database. [Block-type start number] may be set with reference of the

[Number of Block Type]. For example, if the allowed number of block

types is 20 for both FCS0101 and FCS0102, and the [Block-type start

number] for FCS0101 is set to 0, the areas from 0 to 19 is reserved for

FCS0101. Thus the [Block-type start number] for FCS0102 may be set to

20 or greater.

♦ Action when Downloading to IOM

When downloading to an I/O module, the behavior of function blocks

connected to the module may be specified as IOP (input open) or not.

♦ SS-DUAL PV Update during Deviation Alarm

When SS-DUAL block signal selector switch is at the position 3, both

input1 and input2 will be monitored. If one of them is not normal, the

switch will select the normal side input. If a deviation alarm occurs, to

update PV or to hold the current PV can be set by checking this option.

When checking the option box for [SS-DUAL PV Update During Deviation

Alarm], if a deviation alarm occurs when the switch position is 3, the data

status of PV will become BAD but the PV itself will continue to update vary

with the selected input signal. The default setting does not check this

option, so that when a deviation alarm occurs, the SS-DUAL will hold its

current PV. This setting covers all SS-DUAL blocks for the whole FCS.

♦ Alarm Notify Action when All AOF Released

YME Training Center

F-3

CS3KR3-ENG 1 ST Edition Jan 2002