I. REGULATORY CONTROL FUNCTION BLOCKS

constant. Upon online downloading to an FCS, the constants are always

substituted for the current tuning parameters for any changed function block. The

saved tuning parameters take precedence over the constants upon offline

downloading to an FCS, while the constants take precedence over the unsaved

tuning parameters upon initial offline downloading to an FCS.

♦ Example of setting constants.

PH=80,PL=20

I.4. OTHER REGULATORY CONTROL FUNCTION BLOCKS

Figure: Function Block Diagram of Input Indicator Block (PVI)

Figure: Function Block Diagram of Manual Loader Block with Auto/Man SW (MLD-SW)

YME Training Center I-20