The calculated parameters in characteristic points of the analyzed systems are presented in Tables<br />

A.1, A.2, A.3 in appendix A.<br />

5. Results<br />

The crucial calculated parameters at system boundaries of each analysed CHP unit have been<br />

presented in Table 3.<br />

For the same district heat production, obtained net and gross electricity production is the highest for<br />

IGCC unit. The CO2 emission for both plants equipped with CO2 capture is relatively low. Lack of<br />

energy consumption for the CO2 capture installation in case of reference CFB plant results in the<br />

highest value of energy utilization factor achieved. EUF indicator for the IGCC CHP plant is lower<br />

than for other systems as it does not take into account different quality of products.<br />

When comparing exergy efficiency, the highest value is achieved for the reference CFB plant<br />

(without CO2 capture). The decrease of exergy efficiency caused by CO2 capture and compression<br />

is ca. 8 percentage points, but in case of IGCC CHP plant the exergy efficiency plant is only 3<br />

points lower than for the reference system.<br />

Table 3. Results of simulation analysis<br />

Parameter Unit<br />

CFB CHP plant<br />

without CO2 capture<br />

(reference)<br />

123<br />

CFB CHP<br />

plant with<br />

CO2 capture<br />

IGCC CHP<br />

plant with CO2<br />

capture<br />

Total district heat<br />

production MWth 110,22 110,26 110,14<br />

including:<br />

- waste heat MWth 0 53,24 29,22<br />

- steam-fed heat<br />

exchangers MWth 110,22 57,02 80,92<br />

Fuel flow rate kg/s 9,34 10,40 13,02<br />

Fuel chemical energy<br />

(LHV-based) MW 188,29 209,66 262,48<br />

Gross electricity<br />

production MWe 64,70 64,10 113,30<br />

Net electricity production MWe 60,10 50,80 78,40<br />

Electric power<br />

consumption for CO2<br />

compressors MW - 6,10 7,00<br />

CO2 emission from CHP<br />

plant (total) kg/s 18,46 2,06 2,52<br />

CO2 mass flow rate for<br />

transportation (captured) kg/s - 18,49 22,20<br />

EUF (Eq. 1) % 0,90 0,77 0,72<br />

Fuel exergy input MW 205,24 228,53 286,11<br />

District water exergy<br />

increase (Eq. 3) MW 10,36 10,36 10,36<br />

Exergy efficiency (Eq. 2) - 0,35 0,27 0,32<br />

CO2 emission factor per<br />

GJ of produced district<br />

heat (Eq. 4) kgCO2/GJt 48,86 -81,59 -131,95