Fig. 8. Percentage share of electric power produced by steam directed to condenser, district<br />

heating and CO2 capture purposes for the first variant – W1 by different energy<br />

consumption rates of sorbent (2,8 MJ/kgCO2 and 3,89 MJ/kgCO2).<br />

Fig. 9. Percentage share of electric power produced by steam directed to condenser, district<br />

heating and CO2 capture purposes for the second variant – W2 by different energy<br />

consumption rates of sorbent (2,8 MJ/kgCO2 and 3,89 MJ/kgCO2).<br />

Fig. 10. Electric power as function of heating capacity<br />

3.<strong>1.</strong> Heating unit operation<br />

Heating unit is fed from the intermediate pressure turbine outlet. Before integration with a CC unit<br />

outlet water temperature can be regulated only by means of steam throttling at the low pressure<br />

turbines inlet. After integration, pressure at the intermediate turbines outlet has to be kept on a level<br />

that will provide proper temperature for sorbents regeneration. Regulation is realized then by<br />

141