Technical description3Boiler size Unit 800 1000 1200Type approval number – 06-223-769Product ID no. – CE-0085 AU 0452Table 8Specification for the <strong>Logano</strong> <strong>plus</strong> <strong>SB745</strong> floor standing condensing boilers (dimensions page 19 f.)1) Calculated flue gas temperature for cross-sectional calculation to DIN EN 13384 (average value across the series). The actual flue gastemperature may differ from this, subject to burner setting and actual system temperature.2) Figure in brackets is the recommended draught.3) Safety limit (high limit safety cut-out - STB); maximum possible flow temperature = safety limit (STB) – 18 KExample: safety limit (STB) = 100 °C; maximum possible flow temperature = 100 – 18 = 82 °CTechnical guide Floor standing gas/oil condensing boilers <strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong>, <strong>SB615</strong>, <strong>SB745</strong> – 6 720 802 589 (2012/01) 25