Installation99.3.3 Installation dimensions of the <strong>Logano</strong> <strong>plus</strong> <strong>SB745</strong> floor standing condensing boilersBoiler sizeL BR800 kW 1000 kW 1200 kWA HA H1)[mm]1000(800)B GRA V[mm] 2)3)1800(900)1800(1100)LA S [mm] 400(50)A SL BR [mm] Burner length + 200 (800)L RGL RG [mm] 906BInstallationclearancecontrol unit906Fig. 496 720 648 053-16.1TInstallation dimensions of the <strong>Logano</strong> <strong>plus</strong> <strong>SB745</strong>floor standing condensing boilers (dim. in mm;figures in brackets are minimum clearances)A VCableconduit906Length (L)foundations 2300Width (B)foundations 1060 1140Table 40 Recommended wall clearances for siting<strong>Logano</strong> <strong>plus</strong> <strong>SB745</strong> floor standingcondensing boilers (minimum figures inbrackets)1) If using a flue gas silencer, take its installation dimensions intoaccount.2) Factor in dimension L BR (burner length) subject to burneroverhang3) This dimension depends on the burner length.Technical guide Floor standing gas/oil condensing boilers <strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong>, <strong>SB615</strong>, <strong>SB745</strong> – 6 720 802 589 (2012/01) 79