Installation99.3 Installed dimensionsTo ensure condensate drainage, brick or cast concreteboiler foundations should be 5 cm to 10 cm high andcorrespond to the boiler dimensions, and should not reachthe side walls of the installation room to prevent vibrationsbeing transmitted through such contact. Allow extra spacefor measures to provide sound insulation ( page 84 ff.).Select greater wall clearances to enable easy access forinstallation, maintenance and service work.Combustion equipment and flues (for flue gastemperature up to 160 °C) must be positioned far enoughaway or shielded from combustible components andfitted furniture that temperatures in excess of 85 °C aresafely prevented at the rated heating output. Maintain thespecified minimum dimensions.9.3.1 Installation dimensions of the <strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong> floor standing condensing boilers820 1) A 1820 1) A 1400(100)1157 1)400(100)1494 1)200(0)1200 2)(700) 2) 6 720 642 881-29.1ilA 2700(400)L BRBoiler size Clearance A 1 Clearance A 26 720 642 881-30.1ilFig. 46 Installation dimensions of the <strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong>Fig. 45 Installation dimensions of the <strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong>2) Dimensions also subject to the burner length L BR1)Handling dimensions are smaller ( tab. 35 on page 75)floor standing condensing boilers (dim. in mm;figures in brackets are minimum clearances)VM floor standing condensing boilers (dim.in mm; figures in brackets are minimum1) Handling dimensions are smaller ( tab. 35 on page 75)clearances)[mm][mm]50 700 (400) 950 (550)70 700 (400) 1050 (750)90–115 760 (460) 1300 (900)Table 38 Recommended wall clearances for siting<strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong> floor standingcondensing boilers (minimum figures inbrackets)Technical guide Floor standing gas/oil condensing boilers <strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong>, <strong>SB615</strong>, <strong>SB745</strong> – 6 720 802 589 (2012/01) 77

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!