4 Burner4.2.4 Combustion air control for low pollutantemissionsA further important feature of all Logatop VM is thecombustion air control. This regulates the ratio of air togas via a pneumatically activated pressure differentialcontroller ( fig. 25, [1]). This measures the pressuredifferential between the static fan pressure and thepressure in the mixing zone, and if it deviates from the setvalue, the gas pressure is automatically adjusted. Thisresults in excellent combustion with optimum, consistentlyhigh CO 2 levels throughout the operating range. Thecombustion air control also compensates for fluctuationscaused by the system or environmental conditions (e.g.delivery head fluctuations).G1p L23 LFig. 25Function principle of the gas/air compositesystem for constant combustion values of theLogatop VM premix gas burner, using theLogatop VM2.0/3.0 as an exampleG Gas supplyL Combustion air supplyp L Static fan pressure1 Pressure differential control2 Mixing zone3 Fan (modulating operation)6 720 642 881-24.1il32Technical guide Floor standing gas/oil condensing boilers <strong>Logano</strong> <strong>plus</strong> <strong>SB315</strong>, <strong>SB615</strong>, <strong>SB745</strong> – 6 720 802 589 (2012/01)