<strong>ABB</strong> i-bus ® <strong>EIB</strong><strong>Switch</strong>/<strong>dim</strong> <strong>actuator</strong>, <strong>FM</strong><strong>Type</strong>: <strong>6114</strong> U-<strong>500</strong> + 6324-xxParametersThe default setting for the valuesis printed in bold type.General:– Object for backlighting switches text field and status LEDonly text field LED– Behaviour of backlighting at ONbus recoveryOFF– Number of lightscenes 0 / 4 / 6Only for lightscene operation:– Function of auxiliary push button no functionSave lightscenes– Wait state between telegrams by 0activating lightscenes (base 140 ms)Without lightscene operation:– Function of auxiliary push button no functionBacklighting and LED on/off– IR area bluewhiteno IR– Push button action interpreted as 280 ms / 420 ms / ... / 2.1 slong fromActuator:– Status response to switching object no / yes– Status response to object of brightnessvalueno / yes– <strong>Switch</strong> on with minimum brightnessmaximum brightness– Time base for <strong>dim</strong>ming range 127.5 ms / 2 s / 33 s / 9 min / 2.3 h– Factor for <strong>dim</strong>ming range (1...255) 2Separate for each rocker:When lightscenes are assigned:– Rocker is assigned to two lightscenes