<strong>VFD</strong>-F SeriesParameters Functions SettingsFactorySetting Customer00-02 AC Drive Status Indication 2 Bit 0~1: 00: Run led is off and stop Readled is on.01: Run led is blink andstop led is on.10: Run led is on and stopled is blink.11: Run led is on and stopled is off.Bit 2: 1: Jog on.Bit 3~4: 00: Rev led is off and FWDled is on.01: Rev led is blink andFWD led is on.10: Rev led is on andFWD led is blink.11: Rev led is on andFWD led is off.Bit 5-7: ReservedBit 8: Master frequency source viacommunication interfaceBit 9: Master frequency source viaanalogBit10: Running command viacommunication interfaceBit11: Parameter lockedBit12~15: Reserved00-03 Frequency Setting Read only Read00-04 Output Frequency Read only Read00-05 Output Current Read only Read00-06 DC-BUS Voltage Read only Read00-07 Output Voltage Read only Read00-08 Output Power Factor Read only Read00- 09 Output Power (kW) Read only Read00-10 Feedback Signal Actual Read only ReadValue00-11 Feedback Signal (%) Read only Read00-12 User Target Value (Low bit) Read only ReaduL 0-99.9900-13 User Target Value (High bit) Read only ReaduH 0-999900-14 PLC time Read only Read8-2DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED