<strong>VFD</strong>-F Series02 - 02 Stop Method Factory Setting: 00Settings 00:Stop = ramp to stop, E.F. (External Fault) = coast to stop01:Stop = coast to stop, E.F. = coast to stop02:Stop = ramp to stop, E.F. = ramp to stop03:Stop = coast to stop, E.F. = ramp to stop Ramp: The AC drive decelerates the motor to minimum output frequency according to thedeceleration time setting. Coast: The AC drive output instantly stops upon command and the motor free spins until itcomes to a complete stop. External Fault may be enabled by the EF terminal or a Multi-Function terminal. Please referto Pr.04-00 to 04-07. Loss of an ACI signal may cause an E.F condition. Please refer to 02-07.OutputFrequencyMotorspeedFrequencyOutputFrequencyMotorSpeedFrequencyOperationCommandRUNStops accordingto decelerationtimeSTOPTimeFree runningOperationto stopCommand RUN STOPTimeRamp Coast02 - 03 PWM Carrier Frequency Selections Unit: 1Settings 1~10HP 4000~10000Hz Factory Setting: 9000Hz15~30HP 3000~9000HzFactory Setting: 6000Hz≧40HP 2000~6000HzFactory Setting: 4000Hz This parameter sets the carrier frequency of PWM output. The factory setting and settingrange depend on the model type. When the temperature of the heat sink is greater than its limit, the AC drive will automaticlower the carrier frequency to avoid over heating the AC drive.5-10DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED