Parameters Functions Settings02-07 Loss of ACI Signal 00: Decelerate to 0Hz01: E.F.02: Continue operation by thelast frequency command 02-08 Start-up Display Selection Bit0~1: 00 = F LED01 = H LED10 = U LED (specialdisplay)11 = Fwd / RevBit2: 0 = Fwd LED /1 = Rev LEDBit3~5: 000 = 1st 7-step001 = 2nd 7-step010 = 3rd 7-step011 = 4th 7-step100 = 5th 7-stepBit6~7: ReservedFactorySetting01 02-09 Special Display 00: A displays output current of 00AC drive01: U displays DC-Bus voltageof AC drive02: E displays RMS of outputvoltage03: P displays feedback Signal04: PLC display auto procedurestate 02-10 User Defined Coefficient 0.01~160.00 1.0000<strong>VFD</strong>-F SeriesCustomer8 02-11 Flying Start 00: Disable01: Enable (Dc brake disabled) 02-12 Flying Start Frequency 00: Trace from masterfrequency command01: Trace from maximumsetting frequency 01-00 02-13 Master Frequency Memory 00: Do not remember the lastSettingknown frequency01: Remember the last knownfrequency000001DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-5