<strong>VFD</strong>-F SeriesMaster frequency commandOutput frequencyOutput voltage08-07output currentOutput voltageSynchronization attainedTimeActual V/F outputV/F curve settingOutput frequency08 - 08 BB Speed Search Method Factory Setting: 00Settings 00: Trace from top downward01: Trace from bottom upward This parameter determines BB speed search method when multi-function input terminal04-00 to 04-07 is set to BB External interrupt (11 or 12) and activates. BB speed search method is the same with restart speed search after momentary losspower.08 - 09 Auto Restart Times After Fault Factory Setting: 00Settings 00 ~10 This parameter determines the times of auto restart after fault. When AC drive occurs fault (OV, OC or OCC) and fault disappeared automatically, thisparameter allows AC drive reset and runs with the parameter that is set before faultoccurred. If fault occurred times exceed 08-09 setting, AC drive will reject to restart and need to resetby users to keep on running.5-42DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED