<strong>VFD</strong>-F SeriesGroup 9 Communication ParametersParameters Functions Settings 09-00 Communication Address 01-25400:Disable 09-01 Transmission Speed (Baud 00: Baud rate 4800Rate)01: Baud rate 960002: Baud rate 1920003: Baud rate 38400 09-02 Transmission Fault Treatment 00: Warn and keep operating01: Warn and RAMP to stop02: Warn and COAST to stop03: No warning and nodisplay09-03 Over Time Detection duringTransmission00: Disable01: Enable09-04 Communication Format 00: 7-bit for ASCII01: 8-bit for ASCII02: 8-bit for RTU09-05 Even/Odd Parity and Stopping 00: None parity + 2 stop bitParity Setting01: Even parity + 2 stop bit02: Odd parity + 2 stop bit03: None parity + 1 stop bit04: Even parity + 1 stop bit 09-06 Communication OperationCommand 105: Odd parity + 1 stop bitBit0~1: 00: Disable01: Stop10: Start-up11: JOG start-upBit2~3: ReservedBit4~5: 00: No function01: FWD command10: REV command11: Change directioncommandBit6~7: 00: 1 st stepaccel/decel speed01: 2 nd stepaccel/decel speed10: 3 rd stepaccel/decel speed11: 4 th stepaccel/decel speedFactorySetting01010300000000Customer8-16DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED