<strong>VFD</strong>-F SeriesContent Address Function14: Under voltage (Lv)15: EEPROM WRITE failure (cF1)16: EEPROM READ failure (cF2)17: Base Block (bb)18: Motor over load (oL2)19: Reserved20: Software or password protection (codE)21: External emergency stop (EF1)22: Phase-Loss (PHL)23: Low current (Lc)24: Feedback loss (Fbl)25: Reserved26: FAnP (Fan Power Fault)27: FF1 (Fan 1 Fault)28: FF2 (Fan 2 Fault)29: FF3 (Fan 3 Fault)30: FF123 (Fan 1, 2, 3 Fault)31: FF1, 2 (Fan 1, 2 Fault)32: FF1, 3 (Fan 1, 3 Fault)33: FF2, 3 (Fan 2, 3 Fault)34: Gate Drive Low Voltage Protect (Fv)Status of AC drive00: Run LED is off and STOP led is on. (AC Drivestopping)01: RUN LED is blink and STOP led is on. (AC Drivedeceleration to stop)Bit 0-110: RUN LED is on and STOP led is blink. (AC Drivestandby)11: RUN LED is on and STOP led is off. (AC Driverunning)Bit 2 Jog onBit 3~4 00: REV LED is off and FWD led is on. (Forward)01: REV LED is blink and FWD led is on. (Reverse to2101HForward)10: REV LED is on and FWD led is blink. (Forward toReverse)11: REV LED is on and FWD led is off. (Reverse)Bit 5~7 ReservedBit 8 1: Master frequency source via communicationinterfaceBit 9 1: Master frequency source via analog signalBit 10 1: Running command via communication interfaceBit 11 1: Parameter lockedBit 12 ReservedBit 13 ReservedBit 14-15 ReservedDELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-575