How to read the table<br />

Laying <strong>PROFINET</strong> cables<br />

To determine the required minimum separation distance between <strong>PROFINET</strong><br />

cables <strong>and</strong> other electrical cables, proceed as follows:<br />

In the left column (<strong>PROFINET</strong> cables <strong>and</strong> cables <strong>for</strong> ...) select which electrical<br />

cables you wish to lay in parallel with the <strong>PROFINET</strong> cables.<br />

In the right table area (Spacing), select the type of cable separation that you intend<br />

to use.<br />

See the column with the relevant cable separation type <strong>for</strong> the appropriate distance<br />

<strong>for</strong> each cable type. You shall also observe the regulations described below Table 3<br />

<strong>for</strong> different installation areas.<br />

Signal transmission cable<br />

Table 3: Minimum cable spacing according to IEC 61918<br />

18/99<br />

© Copyright by PNO 2009 – all rights reserved<br />

Spacing to <strong>PROFINET</strong> cable<br />

Without or with<br />

non-metal cutoff<br />

bridge<br />

Aluminum<br />

cutoff bridge<br />

Bus signals such as e.g. other<br />

<strong>PROFINET</strong> cables,<br />

PROFIBUS cables, Data<br />

0 mm<br />

cables <strong>for</strong> PCs, programming<br />

0 mm 0 mm<br />

devices, printers Shielded<br />

analog inputs<br />

Power supply cables<br />

Unshielded power supply<br />

200 mm 100 mm 50 mm<br />

cables<br />

Shielded power supply cables 0 mm 0 mm 0 mm<br />

Steel cutoff<br />

bridge