<strong>PROFINET</strong> cable assembly work<br />
As protective ground is part of the general electrical system, it is not described in<br />
more detail in this document. Always observe the applicable st<strong>and</strong>ards <strong>and</strong><br />
regulations!<br />
Notice:<br />
Some <strong>PROFINET</strong> nodes are equipped with a protective ground<br />
connector. These are mainly <strong>PROFINET</strong> nodes with an additional,<br />
higher-voltage power supply. Establish a protective ground connection<br />
in compliance with the applicable regulations <strong>for</strong> these devices.<br />
2.3.2 Functional ground<br />
Functional ground is used to divert electromagnetic interference voltages to ground.<br />
This improves the interference resistance of data transmission. The functional<br />
ground is used to earth the screen of the cable <strong>and</strong> device case so diverting any<br />
interference pickup to ground.<br />
Manuf.<br />
instructions<br />
Manufacturer instructions:<br />
The manufacturer’s documentation will generally provide important<br />
in<strong>for</strong>mation on how to best connect the <strong>PROFINET</strong> node to ground <strong>and</strong><br />
to the equipotential bonding conductor.<br />
Some <strong>PROFINET</strong> nodes are equipped with a functional ground connector terminal.<br />
This terminal is marked with the symbol <strong>for</strong> functional ground. Connect the<br />
functional ground terminal of the <strong>PROFINET</strong> node to the functional ground<br />
connector of the system using a large cross-section cable which is as short as<br />
possible. In many cases, the entire metal construction of the system is used as<br />
functional ground. Other devices use the installation mounting as functional ground.<br />
You shall there<strong>for</strong>e connect the DIN rails of the system to functional ground.<br />
74/99<br />