Manuf.<br />

instructions<br />

<strong>PROFINET</strong> cable assembly work<br />

<strong>PROFINET</strong> Insulation displacement technology usually consists of a<br />

compatible system of connectors, cable <strong>and</strong> stripping tool. You shall<br />

only use components that are part of the manufacturer's system in<br />

order to avoid problems.<br />

The stripping tools <strong>for</strong> different cable types are in some cases identical<br />

in appearance. However, there are often differences in the knife<br />

cartridge that is installed in the stripping tool. The knife cartridge must<br />

be suited to the <strong>PROFINET</strong> cable/connector that is being used. Using<br />

the incorrect cartridge can result in defective connection of the data<br />

wires or screen.<br />

Make sure that the shield is properly connected when mounting the<br />

connector. Shield <strong>and</strong> signal wires shall not have any connection to<br />

each other<br />

Please close the connector carefully.Otherwise the wires can be<br />

damaged <strong>and</strong> short circuits can occur.<br />

Make sure to use only those <strong>PROFINET</strong> cables that have been<br />

approved by the connector manufacturer <strong>for</strong> use with the relevant<br />

connector. This applies in particular to the use of insulation<br />

displacement technology. For IP65 applications make sure that the<br />

cable diameter matches the connector housing. This is m<strong>and</strong>atory to<br />

ensure correct sealing between connector <strong>and</strong> cable.<br />

2.1.2 RJ45 insulation displacement technology<br />

Read the instructions from the connector manufacturer. The<br />

instructions provide valuable in<strong>for</strong>mation on the connector design<br />

which can vary from one manufacturer to another.<br />