Optical measurement<br />

<strong>PROFINET</strong> cable assembly work<br />

• Measure the attenuation of cable <strong>and</strong> connectors to ensure that al<br />

mountingsteps have been made correctly. (Se <strong>PROFINET</strong> Commissioning<br />

<strong>Guideline</strong> )<br />

2.2.9 Other FO connectors<br />

For fiber optic connection in existing plants in many cases a connector BFOC/2,5 is<br />

still in use. The connector is also know under the trade mark "ST ® -Connector". This<br />

connector has been in use as industrial grade connector <strong>for</strong> many years <strong>and</strong> is<br />

available <strong>for</strong> all <strong>PROFINET</strong> fiber types (plastic as well as glass)<br />

Figure 10: BFOC (ST) Connector<br />

The ST connector is a single wire connector with bayonet latch. As both fibers of a<br />

connection are connected individually, special attention has to be taken <strong>for</strong> the<br />

correct assignment of sending <strong>and</strong> receiving fiber.<br />

The mounting of the connector is comparable to the mounting of the SC-RJ<br />

connector.<br />

72/99<br />