IM 4H3B1-01E<br />

EXPLANATION OF SQUARE ROOT:<br />

The µR1800 uses the following square rooting-method:<br />

Let us define the items as follows:<br />

V min = minimum value of recording span (LEFT)<br />

V max = maximum value of recording span (RIGHT)<br />

F min = minimum value of scale (SCL LEFT)<br />

F max = maximum value of scale (SCL RIGHT)<br />

V x = input voltage<br />

F x = scaling value<br />

Fmax<br />

Fmin<br />

F<br />

a<br />

Vmin<br />

b<br />

(Fmax – Fmin ) x 10%<br />

b'<br />

(V max – V min ) x 1%<br />

c<br />

Vmax<br />

7.1 How to Set Input Range and Recording Span<br />

The relationship between V x (input voltage) and F x (scaling value) is as shown in the<br />

graph below (the graph configuration is approximate).<br />

Between b and c in the graph, the following relation exists between F x and V x:<br />

F = (F – F )<br />

V x – V min<br />

x max min<br />

+ F<br />

V max – V min<br />

min<br />

And between a and b, the relation is:<br />

10 (F<br />

F = max – F min)<br />

x (V x – V min ) + Fmin<br />

V max – V min<br />

V<br />

7 - 9<br />

7. BASIC SETTINGS