27.06.2013 Views

Modeles 4370 UR1800 Recorder Instruction Manual

Modeles 4370 UR1800 Recorder Instruction Manual

Modeles 4370 UR1800 Recorder Instruction Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

IM 4H3B1-01E<br />

9.4 How to Change Initial Settings for Digital Printouts<br />

If you selected INT:<br />

The display ‘START=00:00’ will appear. Specify the reference time of the first<br />

periodic printout using the UP/DOWN-keys. Press the ENT-key. Note that you cannot<br />

specify minutes.<br />

Specify which interval between the periodic printouts you prefer. Choose from AUTO<br />

(and the interval depends on the chart speed) or MAN (and you can specify the interval<br />

yourself). Then press the ENT-key. Note that in case of AUTO, the relation between the<br />

chart speed and the printing intervals of periodic printouts will be as shown in the tables<br />

below.<br />

Pen Model<br />

Dot Model<br />

Chart Speed Printing Interval of Periodic Printout<br />

5 to 9 mm/h<br />

10 to 18 mm/h<br />

20 to 36 mm/h<br />

40 to 72 mm/h<br />

75 to 135 mm/h<br />

150 to 180 mm/h<br />

200 to 320 mm/h<br />

360 to 1500 mm/h<br />

more than 1500 mm/h<br />

no printout<br />

every 8 hours<br />

every 4 hours<br />

every 2 hours<br />

every hour<br />

every 30 minutes<br />

every 20 minutes<br />

every 10 minutes<br />

no printout<br />

Chart Speed Printing Interval of Periodic Printout<br />

6 dot 12 dot 18 dot 24 dot<br />

1 to 9 mm/h no printout no printout no printout no printout<br />

10 to 19 mm/h every 8 hrs. every 12 hrs. every 12 hrs. every 24 hrs.<br />

20 to 39 mm/h every 4 hrs. every 8 hrs. every 8 hrs. every 12 hrs.<br />

40 to 50 mm/h every 2 hrs. every 4 hrs. every 4 hrs. every 8 hrs.<br />

51 to 79 mm/h every 2 hrs. every 4 hrs. no printout no printout<br />

80 to 100 mm/h every hour every 2 hrs. no printout no printout<br />

101 to 1500 mm/h no printout no printout no printout no printout<br />

If you selected MAN:<br />

Specify the interval using the UP/DOWN-keys. You can choose from 10, 15, 20, 30<br />

min and 1, 2, 3, 4, 6, 8, 12, 24 hrs. Then press the ENT-key. Note that when the<br />

printing takes more time than the specified interval, printouts may be skipped.<br />

This setting has been completed, but has not been stored yet.<br />

The display ‘*RCD SET*’ will appear. You can now adjust other settings in the SET<br />

UP Mode, by using the ESC-key.<br />

If you selected EXT:<br />

The setting has been completed, but has not been stored yet. The display ‘*RCD SET*’<br />

will appear. You can now adjust other settings in the SET UP Mode, by using the ESCkey.<br />

Make sure to specify this also at the settings of the REMOTE option (see 9.8).<br />

Before leaving the SET UP Mode, you have to store your new settings. Press the ESCkey<br />

to return to the ‘SETUP=RCD’ display and then select the ‘SETUP=END’<br />

display.<br />

Press the ENT-key. Select ‘END=STORE’ to keep your new settings or<br />

‘END=ABORT’ and press the ENT-key. After a few seconds, the Operation Mode will<br />

appear.<br />

9 - 19<br />

9. CHANGING INITIAL SETTINGS