9.2.2 How to Set Upscale/Downscale TC Burnout<br />

The purpose of the following setting is to specify where the pens will move in case of a<br />

TC-burnout. You can choose from moving to the right (UP) or to the left (DOWN).<br />

This is common for every channel. You can select ON or OFF for each channel.<br />

The initial value is ‘UP’, and ‘OFF’ for every channel.<br />

SETTING PROCEDURE:<br />

Enter the SET UP Mode by turning ‘ON’ the power while pressing and holding the<br />

ENT-key until the SET UP display appears.<br />

Use the UP/DOWN-keys to select the display ‘SETUP=B.OUT’. Press the ENT-key.<br />

Select UP or DOWN using the UP/DOWN-keys. Press the ENT-key.<br />

This burnout processing is ON/OFF selectable per channel. Select the channel No. for<br />

which you want to specify this burnout processing. Then press the ENT-key.<br />

Select ON or OFF. Then press the ENT-key. The display ‘*B.OUT SET*’ will appear.<br />

The burnout setting has been completed, but has not been stored yet. You can now<br />

adjust other settings in the SET UP Mode, by pressing the ESC-key.<br />

Before leaving the SET UP Mode, you have to store your new settings. Press the ESCkey<br />

to return to the ‘SETUP=B.OUT’ display and then select the ‘SETUP=END’<br />

display.<br />

Press the ENT-key. Select ‘END=STORE’ to keep your new settings or<br />

‘END=ABORT’ and press the ENT-key. After a few seconds, the Operation Mode will<br />

appear.<br />