9.1.7 How to Select Alarm Hysteresis ON/OFF<br />
The alarm hysteresis is the difference between the levels of alarm occurence and reset.<br />
You can choose between two levels of hysteresis: 0% (=OFF) and approx. 0.5% of the<br />
recording span (=ON) (common for all alarms).<br />
The inititial value is ‘ON’.<br />
High Limit Alarm(H)<br />
1V<br />
Figure 9.5<br />
Alarm generated<br />
Measured value<br />
Low Limit Alarm(L)<br />
1V<br />
Measured value<br />
Alarm generated<br />
Alarm release<br />
Alarm release<br />
Alarm setting value<br />
- - Hysteresis (approx. 0.5%)<br />
- - Hysteresis (approx. 0.5%)<br />
Alarm setting value<br />
SETTING PROCEDURE:<br />
Enter the SET UP Mode by turning ‘ON’ the power while pressing and holding the<br />
ENT-key until the SET UP display appears.<br />
Use the UP/DOWN-keys to select the display ‘SETUP=ALARM’. Press the ENT-key.<br />
Press the ENT-key until the display ‘ALM_HYS=ON’ appears. Select ON or OFF.<br />
After selection, press the ENT-key. The display ‘*ALARM SET*’ will appear.<br />
The alarm hysteresis setting has been completed, but has not been stored yet. You can<br />
now adjust other settings in the SET UP Mode, by using the ESC-key.<br />
Before leaving the SET UP Mode, you have to store your new settings. Press the ESCkey<br />
to return to the ‘SETUP=ALARM’ display and then select the ‘SETUP=END’<br />
display.<br />
Press the ENT-key. Select ‘END=STORE’ to keep your new settings or<br />
‘END=ABORT’ and press the ENT-key. After a few seconds, the Operation Mode will<br />
appear.<br />
NOTE Hysteresis setting is only valid for High and Low alarms. Hysteresis setting for rate-ofchange<br />
alarms and difference alarms will be ignored.<br />
9 - 8 IM 4H3B1-01E