2-byte communication object “Base<br />

setpoint for slaves” which is linked<br />

with the 2-byte communication objects<br />

“Base setpoint - Telegr. temperature”<br />

of the other devices. The manual setpoint<br />

adjustment should then be<br />

disabled for these objects. The operating<br />

modes heating/cooling or frost/<br />

night/comfort must be set exactly the<br />

same on the master and slave devices<br />

by configuring or assigning the same<br />

group addresses to the operating<br />

mode objects.<br />

Offset<br />

If the measured temperature is corrupted<br />

by the self-heating of the panel, an<br />

offset value can be set for the room<br />

temperature measurement (setting<br />

“Offset value in K x 0.1 K”).<br />

The installation site of the panel and<br />

the appropriate selection of parameter<br />

settings is decisive in the accurate recording<br />

of temperatures.<br />

May 2006 67