<strong>ABB</strong> i-bus ® <strong>EIB</strong>/<strong>KNX</strong><br />
<strong>ABB</strong> <strong>Powernet</strong> <strong>EIB</strong>/<strong>KNX</strong><br />
LEANtouch (monochrome),<br />
SMARTtouch (monochrome, colour)<br />
Type: 6x36/30M…, 6x36/100x…, 6x36/100CB…<br />
2-byte communication object “Base<br />
setpoint for slaves” which is linked<br />
with the 2-byte communication objects<br />
“Base setpoint - Telegr. temperature”<br />
of the other devices. The manual setpoint<br />
adjustment should then be<br />
disabled for these objects. The operating<br />
modes heating/cooling or frost/<br />
night/comfort must be set exactly the<br />
same on the master and slave devices<br />
by configuring or assigning the same<br />
group addresses to the operating<br />
mode objects.<br />
Offset<br />
If the measured temperature is corrupted<br />
by the self-heating of the panel, an<br />
offset value can be set for the room<br />
temperature measurement (setting<br />
“Offset value in K x 0.1 K”).<br />
The installation site of the panel and<br />
the appropriate selection of parameter<br />
settings is decisive in the accurate recording<br />
of temperatures.<br />