<strong>ABB</strong> i-bus ® <strong>EIB</strong>/<strong>KNX</strong><br />

<strong>ABB</strong> <strong>Powernet</strong> <strong>EIB</strong>/<strong>KNX</strong><br />

LEANtouch (monochrome),<br />

SMARTtouch (monochrome, colour)<br />

Type: 6x36/30M…, 6x36/100x…, 6x36/100CB…<br />

Parameters: Room thermostat<br />

The default setting for the values<br />

is printed in bold type.<br />

Setpoints heating:<br />

– Base setpoint in °C (16…31) 21<br />

Comfort temperature heating<br />

– Lowering standby operation heating 2<br />

in K (1…15)<br />

– Lowering night operation heating 4<br />

in K (1…15)<br />

– Setpoint frost protection 7<br />

in °C (4…10)<br />

– Level distance from the base level 1…3…5<br />

to the additional level in K<br />

Controlling/Control value heating:<br />

– Output of control value continuously<br />

switched<br />

– Control type Two-position controller<br />

PI controller<br />

Only for two-position controller:<br />

– Hysteresis 0.3K / 0.5K / 0.7K / 1K / 1.5K / 2K<br />

– Lowering of hysteresis Inactive<br />

0.2 K/min<br />

0.1 K/min<br />

0.06 K/min<br />

0.04 K/min<br />

0.03 K/min<br />

0.02 K/min<br />

– Cycle time of the control value in mm:ss 14:50<br />

(03:00…60:00)<br />

Only for continuous controller:<br />

– Change for automatic sending of Inactive / 2% / 5% / 10%<br />

control value<br />

Only for PI controller:<br />

– Control parameters via installation type<br />

free setting of parameters<br />

Only for installation type:<br />

– Type of heating system Warm water heating (1.5K/100min)<br />

Electric heating (1.5K/50min)<br />

Floor heating (4K/200min)<br />

Only for free parameterisation:<br />

– Proportional area 1.0K / 1.5K / 2.0K / 2.5K / 3K / 4K /<br />

6K / 8K / 10K<br />

– Reset time in min. I part inactive / 10 min / 20 min /<br />

30 min / … / 100 min / … / 240 min<br />

Only for switched controller:<br />

– PWM cycle 3min / 5min / 10min / 15min / 20min /<br />

30min / 40min / 50min / 60min<br />

– PWM cycle is 0% up to control value 0% / 10% / 20% / 30%<br />

– PWM cycle is 100% up to control value 70% / 80% / 90% / 100%<br />

– Effective mode Normal<br />

Inverted<br />

Only for additional heating:<br />

– Hysteresis (one-sided) 0.3K / 0.5K / 0.7K / 1.0K / 1.5K / 2.0K<br />

– Cycle time for automatic sending of the 14:50<br />

control value e in mm:ss (03:00…60:00)<br />

– Control value type switched<br />

quasi contin. (1 Byte: 0% or 100%)<br />

– Effective mode Normal<br />

Inverted<br />